Rectifier Chargers GR(B)
Rectifier Chargers GR (B)(TECNED)
From 0.1kW to 15kW
TECNED rectifier/chargers are based on Thyristor + Concept (SCR+IGBT) technology with a galvanic separation transformer, input PF 0.98, low input harmonics (<10%), standard low DC ripple (< 2% for 3-phase systems).
Like all GR-models, the GR(B)-series is short circuit proof, includes high DC protection as standard to protect the load and delivers a steady output voltage under al operating conditions.
Optional built-in batteries up to 9x 12V/100Ah for 110Vdc installations can provide back-up for small and medium installations. In combination with 12V/40AH and 12V/75AH batteries, up to 8 x 2P distributions MCB’s can be fitted for easy implementation.
The GR(B)-series is supplied in a floor standing sheet steel cabinet with bottom cable entry.
The GR(B) series is the basic charger available in the TECNED GR product family with limited options. It strictly adheres to a truly industrial design with convection cooling and is built for 20 years operational life-time.
The TECNED GR (B) Rectifier / Charger series is available from 24Vdc to 650Vdc nominal with up to 100A output in a single enclosure.
TECNED rectifier/chargers are based on Thyristor + Concept (SCR+IGBT) technology with a galvanic separation transformer, input PF 0.98, low input harmonics (<10%), standard low DC ripple (< 2% for 3-phase systems).
Like all GR-models, the GR(B)-series is short circuit proof, includes high DC protection as standard to protect the load and delivers a steady output voltage under al operating conditions.
Optional built-in batteries up to 9x 12V/100Ah for 110Vdc installations can provide back-up for small and medium installations. In combination with 12V/40AH and 12V/75AH batteries, up to 8 x 2P distributions MCB’s can be fitted for easy implementation.
The GR(B)-series is supplied in a floor standing sheet steel cabinet with bottom cable entry.
Features and Benefits
• High power factor IGBT/SCR conversion technology with very low input THDI and build-in galvanic separation transformer.
• Charging characteristic according DIN 41773 (UI)
• High reliable due to failsafe control system and protection circuits
Specifications
• Input voltage single phase: 110 / 120 / 200 / 220 / 230 / 240 / 277V, (2W+E)
• Input voltage three phase: 208 / 220 / 240 / 380 / 400 / 415 / 480V, (3W+E)
• Input voltage range: +15%/-20% (20% start battery operation)
• Nominal input frequency: 50/60 Hz
• Power factor: 0.98
• Efficiency: Up to 95% (depending on DC bus voltage)
• Nominal output voltage: 24, 48, 60, 110 (125), 380 Vdc
• Battery charging characteristic: IU (DIN 41773), T° compensated floating voltage
Sản phẩm cùng mục
Rectifier Chargers GR(B) 19 inch
Rectifier Chargers GR(B) 19 inch (TECNED)
From 0.1kW to 50kW
Rectifier Chargers GR(B)
Rectifier Chargers GR (B)(TECNED)
From 0.1kW to 15kW
TECNED rectifier/chargers are based on Thyristor + Concept (SCR+IGBT) technology with a galvanic separation transformer, input PF 0.98, low input harmonics (<10%), standard low DC ripple (< 2% for 3-phase systems).
Like all GR-models, the GR(B)-series is short circuit proof, includes high DC protection as standard to protect the load and delivers a steady output voltage under al operating conditions.
Optional built-in batteries up to 9x 12V/100Ah for 110Vdc installations can provide back-up for small and medium installations. In combination with 12V/40AH and 12V/75AH batteries, up to 8 x 2P distributions MCB’s can be fitted for easy implementation.
The GR(B)-series is supplied in a floor standing sheet steel cabinet with bottom cable entry.