Products

High-performance 3-phase UPS, 60-500 kW, unity power factor, 96% online efficiency, scalable to 5 MW with up to 10 units in parallel.
The ABB PowerWave 33 is a premium three-phase online UPS for medium and large data centers, industrial plants, and mission-critical infrastructure. It combines class-leading efficiency, excellent input power factor, and low input current distortion — delivering high availability while minimizing impact on the upstream electrical system.
Ranging from 60 to 500 kVA with parallel expansion, the PowerWave 33 is engineered for installations where uptime, efficiency, and power quality all matter equally. It is particularly at home in colocation sites, financial services, and healthcare campuses.
| General Data | |
|---|---|
| Power Range | 60 - 500 kW |
| Output Power Factor | 1.0 |
| Topology | Online double conversion |
| Parallel Configuration | Up to 10 units |
| Input | |
| Nominal Voltage | 3x380/220VAC+N to 3x415/240VAC+N |
| Voltage Tolerance | -10%/+15% (100%), -20%/+15% (80%), -30%/+15% (60%) |
| Input THDi | <= 4% |
| Frequency | 35 - 70 Hz |
| Power Factor | 0.99 |
| Output | |
| Rated Voltage | 3x380/220VAC+N to 3x415/240VAC+N |
| Voltage Distortion | < 2% |
| Frequency | 50 Hz or 60 Hz |
| Overload | 150% load/0.5min, 125%/5min, 110%/20min |
| Unbalanced Load | 100% (all 3 phases independently) |
| Efficiency | |
| Double Conversion | Up to 96% |
| Eco-mode | >= 99% |
| Environmental | |
| Storage Temperature | -25 to +70 deg C |
| Operating Temperature | 0 to +40 deg C |
| Altitude | 1000 m without derating |
| Battery | |
| Type | Sealed lead-acid, maintenance-free or NiCd |
| Standards | |
| Safety | IEC/EN 62040-1 |
| EMC | IEC/EN 62040-2 |
| Protection Rating | IP 20 |